NH4/NO3/SO4 Inlet
flow and Leak Check
Purpose: This check confirms that the SO4 system and the NH4NO3
system are leak tight and that the MFCs for each system are registering the
proper flow rates.
Required Equipment: Bios with high cell and low
cell
Reference: SOPMAN
Leak Check
1.
Open “Set Flags”
from the Tools dropdown window on Site Manager and down SO4 and NH4NO3.
2.
Remove the
cyclone from the NH4/NO3/SO4 inlet and place a 3/8” red plastic cap over the
inlet.
3.
Allow the system
a minute or two to draw the vacuum and then record the reading for the SO4 MFC;
NO3 CH1 MFC; NO3 CH2 MFC and NO3 CH3 MFC from the DAS. All of these readings should be at 0.00 lpm
+/- 0.02
4.
Remove the vacuum
side of the MFCs being analyzed and record the flow rate from the DAS. These readings should match those with the
inlet capped. If the MFC is showing a
reading higher than 0.00 +/- 0.02, then the calibration is off. Refer to the “MFC Calibration SOP”
Flow Check
1.
From the Flow
Checks menu in Site Manager select Flow Audit – the Flow Audit form will open
in a window.
2.
In the Instrument
box select SO4/NH4/NO3 and click the Input Parameters button.
3.
Connect your BIOS
directly to the MFC using the low cell and get 3 stable 10-point average flow
readings. Enter the last of the 3 readings
into the BIOS MFC Flow Rate blank in units of liters per minute (LPM). These readings should each be 1.25 lpm.
4.
Connect your BIOS
to the NH4/NO3/SO4 inlet using the high cell and get 3 stable 10-point
averages. Enter the last flow rate into
the BIOS Inlet Flow Rate blank in units of liters per minute. This flow should total 5.00 lpm (1.25 lpm/MFC
* 4 MFCs)
5.
Review all your
entries for correctness and click the Calculate button.
6.
Review the
calculation result and if all looks ok click the “Yes” under Save Data. If you had an entry error, click “No” under
Save Data and correct the error.
7.
If you need to
check another flow controller click the Yes button under Change Device. If not click Exit to end the check.
8.
If the flow or
leak check fail and you are unable to fix the problem, then close the SM ticket
after recording all results in the flow audit form and open an operations
ticket stating the issue and everything that you have done so far.